The following correction factors are provided for deviating ambient temperatures:
Cross-sections of round conductors
The standard values of the cross-section of round copper conductors as well as the ap-
proximate ratio of metric ISO and AWG/MCM values are shown in the following table.
Standardized cross-sections of round conductors:
ISO cross-section [mm²]
Note
The line corresponds to a value when the connection possibilities are taken into account.
Drive System SD2 - Hardware Description
General Information Regarding the Wiring
Ambient temperature T [°C]
30
35
40
45
50
55
60
0.2
–
0.5
0.75
1.0
1.5
2.5
4.0
6.0
10
16
25
35
50
70
95
–
120
150
185
240
300
Correction factor
1.15
1.08
1.00
0.91
0.82
0.71
0.58
AWG/MCM
Value
Equivalent cross-section [mm²]
24
22
20
18
–
16
14
12
10
8
6
4
2
0
00
000
0000
250 MCM
300 MCM
350 MCM
500 MCM
600 MCM
0.205
0.324
0.519
0.82
–
1.3
2.1
3.3
5.3
8.4
13.3
21.2
33.6
53.5
67.4
85.0
107.2
127
152
177
253
304
169
Need help?