REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
5.2 Gradually replacing A series remote I/O stations with Q series remote
I/O stations
Use the existing A/AnS/QnA/QnAS series master stations without any change, and gradually replace
the existing remote I/O stations with Q series stations by each station.
For network, MELSECNET/10 can be continuously used by utilizing Q series MELSECNET/H modules
in MELSECNET/10 mode, and thus Q series remote I/O stations can be used together with remaining A/
AnS/QnA/QnAS remote I/O stations.

5.2.1 List of MELSECNET/10 modules and the alternative modules

(1) Replacement of the A/AnS series
Network type
Optical loop
Coaxial loop
Coaxial bus
*1
Modules with a serial number (first five digits) of "15012" or later
5
- 36
Station type
AJ71LP21
Remote master
A1SJ71LP21
station
AJ71LP21G
AJ72LP25
AJ72QLP25
A1SJ72QLP25
Remote I/O station
AJ72LP25G
Remote master
AJ71LR21
station
A1SJ71LR21
AJ72LR25
AJ72QLR25
Remote I/O station
A1SJ72QLR25
Remote master
AJ71BR11
A1SJ71BR11
station
AJ72BR15
Remote I/O station
AJ72QBR15
A1SJ72QBR15
A/AnS series
Q series (alternative module)
Replacement not required
QJ72LP25-25 (MELSECNET/10
mode)
QJ72LP25G (MELSECNET/10
mode)
The step-by-step replacement of
the coaxial loop system is not
possible.
Consider the replacement of the
coaxial loop system with the
coaxial bus system.
Replacement not required
QJ72BR15 (MELSECNET/10
mode)
*1
*1
*1