Mitsubishi Electric MELSEC-A Series Manual page 191

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

5
REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
(2) Parameter of multiplexed remote master station
Parameter
name
MELSECNET/10 module
Network type
Starting I/O No.
Network No.
Total number of (slave) stations Total number of (slave) stations
Network
parameter
Network range
assignment
(common
parameter)
Refresh parameters
Routing parameters
*1
The multiplexed remote master station is the station type of the multiplex master system.
Only the following CPU modules support the multiplex master system.
• Process CPU
• Redundant CPU
Description
QnA/QnAS series
MELSECNET/H module
Network type
Starting I/O No.
Network No.
-
Group No.
-
Mode
Monitoring time
BW setting
XY setting
Reserved
station
Network range
designation
assignment
Remote sub-
(common
master station
parameter)
specification
I/O assignment
setting
Supplemental
settings
Refresh parameters
Routing parameters
*1
: Compatible,
: Partial change required, × : Incompatible
Compat-
Q series
ibility
Monitoring time
BW setting
XY setting
Reserved
station
designation
Remote sub-
master station
specification
-
Supplemental
settings
Precautions for replacement
The group No. is not used in the
remote I/O network.
Set to [0].
Set the mode in GX Works2 or GX
Developer network parameters.
Set with the PLC parameter of
each remote I/O station.
5
- 25