Mitsubishi Electric MELSEC-A Series Manual page 223

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

6
REPLACEMENT OF CC-LINK
(2) QnA/QnAS series
Switch name
Station number setting
switch
Mode setting switch
Transmission speed
setting switch
Condition setting switch
Specifications
AJ61QBT11/A1SJ61QBT11
Sets the station No. of the
module.
<Setting range>
• For remote net mode
Master station: 0
Local station: 1 to 64
Standby master station: 1 to
64
• For remote I/O net mode
Master station: 1 to 64 (The
last station No. of remote I/O
station is set.)
Sets the operation status of the
module.
Sets the transmission speed of
the module.
Sets the operation conditions.
<Settings>
• Station type
• Input data status of data link
faulty station
• Number of occupied stations
: Compatible,
QJ61BT11N
Sets the station No. of the
module.
<Setting range>
Master station: 0
Local station: 1 to 64
Standby master station: 1 to 64
Sets the transmission speed
and operating status of the
module.
-
: Partial change required, × : Incompatible
Compat-
Precautions for
ibility
replacement
Sets the last station No. at
remote I/O net mode with
GX Works2 or GX
Developer.
The mode setting and the
transmission rate setting
are performed with one
switch.
The remote net mode and
remote I/O net mode are
specified in GX Works2 or
GX Developer parameter
settings.
The operating conditions
are set in the parameter
settings of GX Works2 or
GX Developer.