6
REPLACEMENT OF CC-LINK
(2) QnA/QnAS series
(a) Input signal
Input signal
AJ61QBT11/A1SJ61QBT11
Xn0
Module error
Xn1
Data link status at host station
Xn2
Parameter setting status
Xn3
Data link status of other station
Module reset acceptance
Xn4
complete
Xn5
Prohibited to use
Data link startup by buffer
Xn6
memory parameter normal
completion
Data link startup by buffer
Xn7
memory parameter error
completion
Data link startup by E
Xn8
parameter normal completion
Data link startup by E
Xn9
parameter error completion
Parameter registration to
XnA
2
E
PROM normal completion
Parameter registration to
XnB
2
E
PROM error completion
XnC
Prohibited to use
2
E
PROM erasure normal
XnD
completion
2
E
PROM erasure abnormal
XnE
completion
XnF
Module ready
X(n+1)0
X(n+1)1
X(n+1)2
X(n+1)3
X(n+1)4
X(n+1)5
X(n+1)6
X(n+1)7
Prohibited to use
X(n+1)8
X(n+1)9
X(n+1)A
X(n+1)B
X(n+1)C
X(n+1)D
X(n+1)E
X(n+1)F
Signal name
QJ61BT11N
Module error
Data link status at host
station
Prohibited to use
Data link status of other
station
Prohibited to use
Prohibited to use
2
PROM
Prohibited to use
2
PROM
Prohibited to use
Prohibited to use
Module ready
Prohibited to use
: Compatible,
: Partial change required, × : Incompatible
Compat-
Precautions for replacement
ibility
Delete the sequence program of the section
corresponding to the function, and check with
SB006D (Parameter setting status).
Delete the sequence program of the section
corresponding to the function.
×
When the switch setting is changed, turn the power
supply of programmable controller system OFF 
ON or reset the programmable controller CPU.
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).