Mitsubishi Electric MELSEC-A Series Manual page 189

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

5
REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
(2) Remote I/O station switch settings comparisons
Switch name
A/AnS/QnA/QnAS series
MELSECNET/10 module
Sets the mode.
<Setting range>
0: Online
2: Offline
3: Loop test (forward loop)
4: Loop test (reverse loop)
Mode setting
5: Station-to-station test
switch
(master station)
6: Station-to-station test
(slave station)
7: Self-loopback test
8: Internal self-loopback test
9: H/W test
F: Station No. check
Condition
Sets the operation conditions.
setting switch
*1
Modules with a serial number (first five digits) of "15012" or later supports Online (MELSECNET/10 mode).
Description
Q series
MELSECNET/H module
[Using QJ72LP25-25]
Sets the mode.
<Setting range>
0: Online (10Mbps)
1: Self-loopback test (10Mbps)
2: Internal self-loopback test
(10Mbps)
3: Hardware test (10Mbps)
4: Online (25Mbps)
5: Self-loopback test (25Mbps)
6: Internal self-loopback test
(25Mbps)
7: Hardware test (25Mbps)
8: Online (MELSECNET/10
*1
mode)
[Using QJ72LP25G and
QJ72BR15]
Sets the mode.
<Setting range>
0: Online
1: Self-loopback test
2: Internal self-loopback test
3: Hardware test
8: Online (MELSECNET/10
*1
mode)
-
: Compatible,
: Partial change required, × : Incompatible
Compat-
Precautions for replacement
ibility
• Set offline and loop test in GX
Works2 or GX Developer
network parameters.
• Substitute the forward loop/
reverse loop test for the station-
to-station test.
• Check network No., group No.
and station No. in GX Works2 or
GX Developer network
diagnostics (host information).
Nothing to be noted for the
MELSECNET/H.
5
- 23

Advertisement

Table of Contents
loading

Table of Contents