REPLACEMENT OF CC-LINK
6.5 Parameter Comparisons
(1) A/AnS series
Parameter name
Network parameter
Automatic refresh
parameter
(2) QnA/QnAS series
Parameter name
Network parameter
Automatic refresh
parameter
*1
Parameter setting of Q series CC-Link modules
Parameters can be set on up to eight modules using GX Works2 or GX Developer. For the settings of the 9th module or
later, use the dedicated instruction.
For details, refer to the CC-Link System Master/Local Module User's Manual.
*2
Delete the program for the network parameter setting of the existing module.
6
- 11
Specifications
AJ61BT11/A1SJ61BT11
Set this parameter with the
sequence program (TO
instruction) or with dedicated
instruction (RLPA instruction).
Read/write cyclic data with
FROM/TO instruction or set
this parameter with dedicated
instruction (RRPA instruction).
Specifications
AJ61QBT11/A1SJ61QBT11
Set this parameter with GX
Developer or sequence
program (TO instruction).
Perform the automatic refresh
setting with GX Developer or
read/write cyclic data with
FROM/TO instruction.
: Compatible,
QJ61BT11N
Set this parameter with GX
Works2/GX Developer or with
dedicated instruction
(RLPASET instruction).
Perform the automatic refresh
setting with GX Works2/GX
Developer or read/write cyclic
data with FROM/TO
instruction.
: Compatible,
QJ61BT11N
Set this parameter with GX
Works2/GX Developer or with
dedicated instruction
(RLPASET instruction).
Perform the automatic refresh
setting with GX Works2/GX
Developer or read/write cyclic
data with FROM/TO
instruction.
: Partial change required, × : Incompatible
Compat-
Precautions for
ibility
replacement
Newly set the parameter
with GX Works2/GX
Developer or the dedicated
instruction (RLPASET
*1 *2
instruction).
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Perform the automatic
refresh setting with GX
Works2/GX Developer or
read/write cyclic data with
FROM/TO instruction.
When setting the network
parameter with dedicated
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.
: Partial change required, × : Incompatible
Compat-
Precautions for
ibility
replacement
Newly set the parameter
with GX Works2/GX
Developer or the dedicated
instruction (RLPASET
*1 *2
instruction).
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Set the automatic refresh
with GX Works2/GX
Developer or read/write
cyclic data with FROM/TO
instruction.
When setting the network
parameter with dedicated
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.