Operation in the Operating State
8.9 Control System on Site
[sc_security_password_confirmationID, 2, en_US]
Figure 8-74
Table 8-13
Name
Settings/operation
Fct.Key/PB operation
Switching (process)
Switching (unlocked)
Switching authority
Switching (without synchro-
check)

Control with Function Keys

8.9.11
8 of 9 function keys can also be used for control. Function key <F9> is hardcoded for language switching.
Using a function key you can initiate a switching sequence, for example, to switch on a feeder.
You reach the function keys by pressing the blue <Fn> key and the corresponding digit from <1> to <9>
in the numerical keypad.
Define your switching sequence using the CFC editor.
Link a single command (type SPC) in the information routing matrix with the desired function key.
Connect this single command with a SPC_INFO block that starts the switching sequence.
210
Assignment of Confirmation IDs
Confirmation IDs
Description
Authorization to change settings on the device display and DIGSI 5
Access to process data is possible with the help of push-buttons and func-
tion keys. The confirmation ID of Settings/operation is requested.
To prevent unintentional switching of combined protection and control
devices, this general authorization for switching on site is available.
Release for manual placement of markers
Only in devices without key switch authorization for unlocked switching
(only effective in devices with parameterized switchgear interlocking
protection conditions)
Only in devices without key switch release of On-site switching authority,
and hence of control on the device display
Authorization for unsynchronized switching of a circuit breaker (only in
devices with activated synchrocheck)
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020