Siemens SIPROTEC 5 Manual page 207

V8.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[scstatus-310816-01, 1, en_US]
Figure 8-68
[scstatu2-310816-01, 1, en_US]
Figure 8-69
The manually updated position of the switching device will be displayed.
[scstatu3-310816-01, 1, en_US]
Figure 8-70
NOTE
i
i
For security reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.
NOTE
i
i
Setting acquisition blocking and the subsequent manual updating are also possible via the IEC 61850
system interface.
You can also set acquisition blocking via a binary input. If you want to put the feeder or the switching device
in revision, you can set the acquisition blocking for an individual or several switching devices with an external
toggle switch. For this purpose, every switching device in the Switch function block (circuit breaker or discon-
nector switch) has the input signal >Acquisition blocking. This signal can also be set from the CFC.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Activating Manual Update
Selecting Position
Position of the Switching Device
Operation in the Operating State
8.9 Control System on Site
207