Operation in the Operating State
8.7 Fault Recording
[scusrrec-051016-01, 1, en_US]
Figure 8-42
You can also set parameters for the start criterion via an external start signal in the Fault recorder func-
tion. >External start). With this you can, for example, initiate recording of a fault record using an
external protection device without internal fault recording in case of pickup.
A test fault record can also be initiated manually and directly via the on-site operation panel of the device
(for example, via function key) or via DIGSI 5. For this, a freely configurable starting signal (>Manual
start) is available.
[scmnstrt-051016-01, 1, en_US]
Figure 8-43
Fault recording can also be initiated via communication. This can happen via the standards IEC 61850 and
IEC 60870-5-103 through a connected substation automation technology system.
188
User-Defined Configuration of the Start Criterion for Fault Recording
Manual Start via DIGSI 5
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020