Measurement of the motor statistics starts when the motor state changes to Start. Measurement of the
motor starting time ends as soon as the motor state changes to Standstill or Running. The motor state is
obtained from the Motor-state detection function.
No entry is recorded in the motor-starting log if the motor state changes to Start and the current drops
below the motor starting current within 500 ms.
Table 8-8
Measured Values
Start duration
Starting current
Starting voltage
Reading from the PC with DIGSI 5
Use the project-tree window to reach the motor-starting log of your SIPROTEC 5 device.
Project → Device → Process data → Logs → Motor-starting log
The state of the motor-starting log last loaded from the device is shown to you.
To update (synchronization with the device), click the Read log entries button in the headline of the
indication list
[scmotmlp-160713-01, 2, en_US]
Figure 8-33
Reading on the Device through the On-Site Operation Panel
To reach the motor-starting log from the main menu, use the navigation keys of the on-site operation
panel.
Main Menu → Indications → Motor-starting log
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Motor-Starting Log
Motor starting time
Motor-starting current (primary)
Motor-starting voltage (primary)
(Figure
8-33).
Reading the Motor-Starting Log with DIGSI 5
Operation in the Operating State
8.5 Logs
Primary
s
A (or kA)
V (or kV)