Initializing Device And Verifying Basic Status - Siemens SIPROTEC 5 Manual

V8.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Procedure for checking device parameterization:
Check whether the parameterized hardware coincides with the existing devices. In the project, click
²
Devices and networks.
If you communicate via Ethernet, check the correct setting of the IP addresses simultaneously. You can
²
also do these checks under Device.
If the project is an IEC 61850 system, go to menu item IEC 61850 GOOSE Communication to familiarize
²
yourself with the respective circuitry. If you use circuiting you can view the static reports on the systems
control.
Create an overview of the settings or the routing in the individual menu items. Siemens recommends
²
doing this when opening the device in DIGSI.

Initializing Device and Verifying Basic Status

9.3.3
SIPROTEC 5 devices are initialized via the front USB interface. Alternatively, you can initialize the devices via
port J. If you connect port J to a system, you must change the previous IP address.
Connect the device to the corresponding USB interface of your computer.
²
In the DIGSI 5 operating program right-click the device to be initialized.
²
Click the Load Configuration in Device menu item.
²
DIGSI 5 then accepts the connection to the device and loads the complete parameterization into the device.
This process takes some time.
[scstartsc-270814-01, 1, --_--]
Figure 9-11
Once the transfer is completed, the device executes a reset and is in the startup mode. Once this status is
finished, the display image appears and the green LED (Run) lights up. The red LED (Error) must be off.
The display image contains information about the basic device type, for example, transformer protection, the
firmware version (FW), and the loaded parameterization version. In SIPROTEC 5, this is called Configuration
(CFG).
If a display image is adjusted in the parameterization, then the device switches to this display state after
several seconds. The set display image, for example, the measured-value display, should appear.
If you wish verify the loaded parameterization randomly, you can execute a check through the on-site opera-
tion panel. Log in and follow the menu. Read the user instructions in chapter
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Display during Transfer
Commissioning
9.3 Initial Startup
5 Using On-Site Operation
Panel.
223