Operation in the Operating State
8.4 Indications

Spontaneous Indication Display in DIGSI 5

8.4.5
With DIGSI 5 you have the possibility of displaying all currently transmitted indications of the selected device
in a special indication window.
Procedure
Call up the spontaneous indications of your selected device in the navigation window under Online
access.
Click Indications in the path:
Online access → Interface → Device → Indications
The raising indications appear immediately without you having to wait for a cyclical update or initiate the
manual update.
[scspnmld-230211-01, 2, en_US]
Figure 8-8

Spontaneous Fault Display on the On-Site Operation Panel

8.4.6
After a fault, the most important data of the last fault can be displayed automatically on the device display
without further operational measures. In SIPROTEC 5 devices, protected objects and even circuit breakers can
be freely created and configured depending on the application (even several instances). In DIGSI 5, several
spontaneous fault displays can be configured, depending on the application, with each individual one being
assigned a particular circuit breaker. These displays remain stored in the device until they are manually
confirmed or released by LED reset.
Configuration of a Spontaneous Fault Display with DIGSI 5
To reach the Fault-display configuration of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Display pages → Fault-display configuration
In the main window, all configured circuit breakers are displayed. A list of a maximum of 6 configurable
display lines is offered for each circuit breaker. The activation of a spontaneous fault display occurs for
each circuit breaker by selection via checkmark in the column Display.
With the parameter (_:139) Fault-display (under Device → Parameter → Device settings) you
determine whether spontaneous fault displays should be shown for each pickup or only pickups with the
trip command.
152
Displaying Spontaneous Device Indications in DIGSI 5
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020