Mains Input Electrical Specifications; Bypass Input Electrical Specifications - Huawei UPS5000-E-30K-FM User Manual

Hide thumbs Also See for UPS5000-E-30K-FM:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual

8.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage range
Rated frequency
Input frequency range
Input power factor
THDi

8.6 Bypass Input Electrical Specifications

Item
Rated input voltage
Input voltage range
Input system
Rated frequency
Frequency range
Issue 01 (2020-04-27)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
50 Hz / 60 Hz
40–70 Hz
Specifications
380 V AC, 400 V AC, or 415 V AC (line voltage)
Upper threshold: +10%, +15% (default), +20%, +25%
(when the voltage system is 380 V AC)
Upper threshold: +10%, +15% (default), +20% (when the
voltage system is 400 V AC)
Upper threshold: +10% (default), +15% (when the voltage
system is 415 V AC)
Lower threshold: –10%, –15%, –20% (default), –30%,
–40%, –50%, –60%
Three-phase, four-wire, and PE
50 Hz / 60 Hz
50/60 Hz ± 6 Hz (adjustable, 0.5–6 Hz, ± 2 Hz by default)
Copyright © Huawei Technologies Co., Ltd.
At 30–40° C: The UPS works at full load when the
voltage is 187–280 V AC and is derated to 40%
load when the voltage is 187–80 V AC.
At 0–30° C: The UPS works at full load when the
voltage is 176–280 V AC and is derated to 40%
load when the voltage is 176–80 V AC.
> 0.99 (full load)
> 0.98 (half load)
≤ 3% (linear load)
≤ 5% (non-linear load)
8 Technical Specifications
164

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-120k-fm

Table of Contents