Huawei UPS5000-E-30K-FM User Manual page 124

Hide thumbs Also See for UPS5000-E-30K-FM:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Figure 4-37 Maintenance 2
Battery Maint. screen
Battery maintenance includes Forced Equalized Charging, Shallow Dis. Test, and Capacity
Test.
Figure 4-38 Battery Maint. screen
Issue 01 (2020-04-27)
On the System Info > Settings > iBOX Settings > Basic Param. screen, if the Number of iBOXs
is not 0 the Maintenance is displayed on the iBOX Control screen.
Choose Monitoring > Param. Settings > System Settings on the WebUI, if the Bus capa. life is set
to Enable, the Maintenance is displayed on the Bus Capa. Life screen.
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Copyright © Huawei Technologies Co., Ltd.