UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Figure 4-31 Basic Param.
Item
Number of
iBOXs
Start address
for iBOX-NMS
communication
iBOX number
of iBATs
Figure 4-32 Advanced Param.
Item
Current source
Batt. abnormal
BCB trip
Issue 01 (2020-04-27)
Description
The number of iBOXs connected
to UPS.
Specifies the communication
address when the northbound
device queries iBOX data.
Specifies the number of iBATs
managed by the iBOX.
Description
Specifications of the Hall effect
sensor used to detect iBOX
current.
Specifies whether BCB trips
when batteries are abnormal.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0–6
0
0–124
0
0–300
Default Value
Value Range
Hall sensor
Hall sensor
200A
200A, Hall
sensor 600A
Disable
Disable, Enable