3.1.1.2 Installation Environment
3.1.1.3 Installation Clearances
Reserve the following clearances around the cabinet to facilitate operations and ventilation:
Figure 3-2 Reserved clearances (unit: mm)
3.1.2 Tools and Instruments
Insulate installation tools to prevent electric shocks.
Issue 01 (2020-04-27)
Do not install the UPS in high temperature, low temperature, or damp environments.
Install the UPS away from water sources, heat sources, and flammable or explosive
materials. Keep the UPS away from direct sunlight, dust, volatile gases, corrosive
materials, and air dense with salt particles.
Do not install the UPS in environments with conductive metal scraps in the air.
The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30° C. Operating temperatures higher than 30° C shorten the battery
lifespan and operating temperatures lower than 20° C reduce the battery backup time.
Reserve at least 800 mm from the front of the cabinet to facilitate ventilation and
operations. Reserve at least 500 mm from the rear of the cabinet for facilitate ventilation.
Reserve at least 500 mm from the top of the cabinet for operations.