UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Item
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
Sched. shallow
dis. test
Sched. shallow
dis. test time
Sched. shallow
dis. test interval
(d)
Shallow dis.
test dis. ratio
(%)
iBOX Settings
Figure 4-30 iBOX Settings
Issue 01 (2020-04-27)
Description
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Time for scheduled shallow
discharge test.
Interval for scheduled shallow
discharge test.
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
On the System Info > Settings > iBOX Settings > Basic Param. screen, if the Number of iBOXs is
not 0 the Batt. String Config is displayed on the iBOX Settings screen.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
1.80 V/cell
1.8–1.9
1.75 V/cell
1.75–1.85
1.60 V/cell
1.6–1.75
Disable
Disable, Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
60
30–90
20
10–50
110