Figure 3-29 Mounting holes for the cable entry cabinet (unit: mm)
Step 2 Remove the right and rear covers from the UPS cabinet, and remove the front and rear covers
from the cable entry cabinet. Put away the removed screws and covers.
Step 3 Adjust the anchor bolts of the cable entry cabinet to make it flush with the UPS cabinet.
Step 4 Install equipotential plate mounting kits on the same horizontal plane of the UPS cabinet and
cable entry cabinet.
Issue 01 (2020-04-27)
This section describes how to install the cable entry cabinet on the right side of the UPS. If the cable
entry cabinet needs to be installed on the left side of the UPS, remove the side panel of the cable entry
cabinet and the cable trough, and install them on the right side of the cable entry cabinet.
shows the positions of the side panel of the cable entry cabinet and the cable trough.