Huawei UPS5000-E-30K-FM User Manual page 40

Hide thumbs Also See for UPS5000-E-30K-FM:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Figure 2-16 Monitoring interface card
Table 2-6 Ports on the monitoring interface card
Port
DO_1
DO_2
DO_3
DO_4
DB26
Battery temperature
sensor port
Southbound
communications port 1
Southbound
communications port 2
Network port
Issue 01 (2020-04-27)
DO_1 to DO_4 meet the maximum voltage and current requirements of 30 V DC/1 A or 60 V DC/0.5 A.
Copyright © Huawei Technologies Co., Ltd.
Silk
Description
Screen
NO
DO_1, DO_2, DO_3, and DO_4 indicate
alarm outputs. Their default values are Critical
COM
alarm, Minor alarm, Bypass mode, and Battery
mode, respectively.
NO
It can be set to Disable, Critical alarm,
COM
Minor alarm, Bypass mode, Battery mode,
Low batt. volt., Low battery SOC,
NO
Abnormal mains, Sys maint breaker enable,
Sys outp breaker enable, Maint. breaker
COM
closed, No power supplied, Mains supplies
NO
power, ECO mode, Battery test, and Batt.
Volt. Below Thres..
COM
Configure power segment settings based on
backup time.
MDU
Provides FE, RS485, I2C, and CAN signals.
B_TEMP
Connects to an indoor battery temperature sensor.
COM1
Supported protocol: Modbus-RTU.
Connects to an ambient temperature and
humidity sensor over two wires.
COM2
Supported protocol: Modbus-RTU.
Connects to a southbound device, such as an
iBattery.
FE
Supported protocols: Modbus-TCP, HTTPS,
and SNMP.
Connects to the network port on a PC.
2 Overview
32