Wilo -SiFire FIRST Installation And Operating Instructions Manual page 57

Table of Contents

Advertisement

M02 – General
Start delay from pressure switch
P02.03
Delayed departure from priming float
P02.04
Waiting time automatic stop from priming float
P02.05
Rated aux voltage
P02.06
Minimum aux voltage threshold
P02.07
Maximum aux voltage threshold
P02.08
Aux voltage alarm delay
P02.09
Waiting time automatic stop from pressure
P02.10
switch
Analogue AINx channel for water level monitoring
P02.15
in the storage tank
Low water level threshold in the tank
P02.16
Treshold for water level in cooling circuit
P02.17
Water level threshold for
P02.18
Maximum number of pilot starts
P02.19
Maximum pilot pump operating time
P02.20
Alarm delay A56-A57 .
P02.21
M03 – PASSWORD
Enabling password for menu access
P03.01
User level password
P03.02
Advanced level password
P03.03
Remote access password
P03.04
M04 – Ambient temperature
Room temperature reading -Defines the source
from which the room temperature measurement
is taken. OFF = measurement disabled. INT =
P05.01
measurement from sensor incorporated in the
control unit. EXT = temperature measurement
taken from NTC remote probe connected to ter-
minals 53 and 54.
Minimum temperature alarm threshold for alarm
P05.02
A46
Minimum temperature alarm delay for alarm A46
P05.03
Maximum temperature alarm threshold for alarm
P05.04
A47
Maximum temperature alarm delay for alarm A47
P05.05
Room heater start threshold
P05.06
Room heater stop threshold
P05.07
Heater start/stop delay
P05.08
M05 – Batteries
Rated battery voltage
P05.01
MAX voltage limit
P05.02
MIN voltage limit
P05.03
MIN/MAX voltage delay
P05.04
Battery boost interval
P05.05
Battery boost duration
P05.06
Installation and operating instructions Wilo-SiFire FIRST
Switchgear of diesel pump
Unit
S
S
S
VAC
%
%
S
S
%
%
S
Min.
S
Unit
Unit
°
S
°
S
°
°
S
Unit
V
%
%
S
H
Min.
Standard
Area
1.0
0.0-60.0
1.0
0.0-60.0
OFF
OFF/1 ... 10000
230
100-240
75
OFF/50-100
120
100-130/OFF
30
0-600
OFF
OFF/0...10000
OFF
OFF/1-4
20
0-100
10
0-100
60
0...10000
OFF
OFF/0...10000
OFF
OFF/1...1000
60
1-1000
Standard
Area
OFF
OFF – ON (PRESET)
1000
0-9999
2000
0-9999
OFF
OFF/1-9999
Standard
Area
INT
OFF
INT
EST
4
0-70
10
0-600
40
0-160
10
0-600
8
0-70
10
0-70
10
0-600
Standard
Area
12
12/24
130
110-140
75
60-130
10
0-120
168
1-1000
60
1-240
en
57