en
9.3
Overview of the most important
parameters
M01 – Utilities
Language – Language selection for the texts on
the display
P01.01
Power on clock setup - Activate automatic access
P01.02
to clock setup after power up
Display contrast - Adjusting the contrast of the
P01.03
LCD display
High display backlight intensity
P01.04
Low display backlight intensity
P01.05
Low backlighting transition delay
P01.06
Return to default page - Delay in resetting the
P01.07
default page display. If set to OFF the display al-
ways remains on the last manually selected page
Default page - Default page shown on the display
P01.08
at power on and after the delay.
Electric pump description
P01.09
These parameters are accessible with user level passwords.
M02 – General
Rated voltage
P02.01
Type of connection
P02.02
Rated frequency
P02.03
Rated current
P02.04
Rated power
P02.05
Primary TA
P02.06
Secondary TA
P02.07
TA measurement
P02.08
Type of start-up
P02.09
Reduced start-up time
P02.10
Top interlock time, between reduced voltage and
P02.11
full voltage
Temperature unit of measurement
P02.12
Start delay from pressure switch
P02.13
Delayed departure from priming float
P02.14
Maximum pilot pump operating time
P02.21
Delay A25-A26 - Alarm activation delay A25
P02.22
Pump not under pressure and A26 Pump under
pressure.
42
Electric pump switchgear
The controller is programmed and preset at the factory for fully automatic operation.
However, some of the main parameters contained in the respective menus are:
Unit
%
%
%
S
S
Unit
VAC
Hz
A
kW
A
A
S
S
S
S
Min.
S
Standard
Area
English
English
Italian
French
Spanish
German
OFF
OFF - ON
50
0-100
100
0-100
25
0-50
180
5-600
300
OFF/10-600
Global
(pages list)
FFL
String 20 char.
Standard
Area
400
110...600
L1-L2-L3
L1-L2-L3-N
L1-L2-L3
50
50/60
10.0
0.1...1000.0
AUT
AUT / 1.0...1000.0
5
1...5000
5
1 or 5
3-TA
1-TA-L1 (PRESET)
1-TA-L2
1-TA-L3
3-TA
Star-delta
Star-delta
Direct (PRESET)
Static
Impedances
Autotransformer
15
1...60
0.10
0.02 ... 0.50
°C
°C / °F
1.0
0.0-60.0
1.0
0.0-60.0
OFF
OFF/1...1000
60
1-1000
WILO SE 2020-12
Need help?