Mandik FDMA PM Manual page 9

Fire damper
Hide thumbs Also See for FDMA PM:
Table of Contents

Advertisement

Nominal voltage
Power consumption - motoring
- holding
Dimensioning
Protection class
Degree of protection
Running time - motor
- spring return
Ambient Temperature
- normal duty
- safety duty
- non-operating temperature
Connecting - motor
- auxiliary switch
Thermal trips
Design .41 or .51 with actuating mechanism can be complemented with smoke detector
ORS 142 K. The voltage can be AC 230 V or 24 V DC. Design with voltage AC 230 V is equpped
with Communication and supply device BKN 230-24-MOD and with actuating mechanism BF
24-TN (BFL 24-T, BFN 24-T).
The smoke detector is activated when smoke spreads in air duct system. Deactivation of smoke
detector is provided by interruption of supply voltage for min. 2s.
Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches..
Operating voltage
Residual ripple
Power Consumption Socket
(without actuating mechanism)
Degree of protection
Ambient temperature
Aditional temperature senzor
Connection - net
- motor
- communication and supply device BKN
AC 24 V 50/60 Hz
DC 24 V
7 W
2 W
10 VA (Imax 8,3 A @ 5 ms)
III
-30°C ... +50°C
The safe position will be attained up to max. 75°C
-40°C ... +50°C
cable 1 m, 2 x 0,75 mm²
cable 1 m, 6 x 0,75 mm²
(BF 24-T-ST) with plug-in connectors
Tf1: duct outside temperature Duct +72°C
Tf2/Tf3: duct intside temperature Duct +72°C
Cabel 1m, connected to terminals 1, 2 and 4
Actuator connected on the terminals 2 and 5
Cabel 1m, connected to terminals 1, 2, 4 and 5
9
AC 230 V 50/60 Hz
8 W
3 W
12,5 VA (Imax 500 mA @ 5 ms)
II
IP 54
120 sec
~ 16 sec
18 ... 28 V DC
≤ 200 mV
max. 22 mA
IP 42
-20°C ... +75°C
+70°C