Mandik FDMA PM Manual page 12

Fire damper
Hide thumbs Also See for FDMA PM:
Table of Contents

Advertisement

BAT
Design .61 with communication and supply device can be complemented with smoke detector
ORS 142 K. For supply and comunnication is used BKN 230-24-C-MP, which together with the
BF 24TN-ST (BFL 24T-ST, BFN 24T-ST ) enables central control and checks of fire damper by
means of a simple 2-conductor wiring and it also allows connection to the system via MP-BUS
communication. More information in the Belimo catalog.
Nominal voltage
Power consumption
Dimensioning
Protection Class
Degree of protection
Ambient temperature
Non-operating temperature
Connection - net
- motor
- terminal board
BAT
1
1)
Bridge has been installed by the manufacturer. If needed, it can be
1)
1)
2
removed ad replaced with a thermoelectric starting mechanism. If
3
terminals 1 and 2 are not interconnected, safety function is initiated.
2)
4
2)
Bridge can be used only for starting and without BKS24... !
5
a
6
Two conductor wiring to BKS24
b
7
10 VA (including actuating mechanism with spring return)
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm²
External smoke detector, +24 V, max. 50 mA
1
External smoke detector, control input
2
3
Connection of more BKN devices as slaves
4
GND
5
MP-BUS
a
6
7
b
12
AC 230 V 50/60Hz
3,5 W (operating position)
II
IP 40
-20°C ... +50°C
-40°C ... +80°C