Mandik FDMA PM Manual page 86

Fire damper
Hide thumbs Also See for FDMA PM:
Table of Contents

Advertisement

POSITION:
1
Fire damper FDMA PM
2
Gypsum plate
3
Mineral wool (type depending on the type of construction)
4
Fire resistant foam
5
Stucco plaster
Used materials - example*:
3 - HILTI CFS-F FX - EIS 60
PROMAFOAM-C - EIS 45
SOUDAL, Soudafoam FR-B1 - EIS 30
DenBraven, Fire resistant foam PUR - EIS 30
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
≥ 50
≥ 40
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
≥ 50
≥ 40
86
≥ 100
≥ 100