Download Print this page
Mandik FDMC Installation Instructions Manual

Mandik FDMC Installation Instructions Manual

Fire damper
Hide thumbs Also See for FDMC:

Advertisement

Quick Links

Advertisement

loading

Summary of Contents for Mandik FDMC

  • Page 2 FIRE damper type FDMC, is in all variants classified: as EI 60 ve, ho (i o) S acc. EN 13501-3 and tested acc. EN 1366-2 and acc. EN 15650 Installation in a solid wall construction ≥ 100 ≥ 40 Fire damper FDMC...
  • Page 3 Installation in a gypsum wall construction Installation opening perimeter has to be reinforced by standard drywall profiles. Fire damper FDMC ≥ 50 Gypsum plate ≥ 40 Fire resistant insulation Mineral stone wool min. density 140 kg/m Fire protection mastic min. thick-...
  • Page 4 Damper casing Damper blade Inspection hole covering BAT thermoelectrical starting mechanism Actuating mechanism 1. All fire dampers have to be closed during installation process. 2. The control mechanism has to be protected (covered) against damage and pollution during installation process. 3.
  • Page 5 Placement of the openings in the wall. Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded. Back-to-back air - conditioning piping must be hung or supported so as all load transfer from the back-to-back piping to the damper is absolutely excluded.
  • Page 6 11. Damper blade overlaps. The blade of fire damper exceeds body of fire damper by the value “a”. There has to be enough space in duct for blade rotation. 12. Electrical components, wiring diagrams. S1 S2 <5° <80° N L1 S1 S2 <5°...
  • Page 7 13. Before entering the dampers into operation after assembly and after sequential revisions, checks and functionality tests of all designs including operation of the electrical components must be done. After entering into operation, these revisions must be done according to requirement set by national regulations.
  • Page 8 MANDÍK, a.s. Dobříšská 550 26724 Hostomice Czech Republic Tel.: +420 311 706 706 e-mail: mandik@mandik.cz www.mandik.com All rights reserved by Manufacturer. Changes to the product can be applied. The current product information are available on www.mandik.cz...