Mandik FDMA PM Manual page 69

Fire damper
Hide thumbs Also See for FDMA PM:
Table of Contents

Advertisement

Installation frame E1 is suitable for:
● Solid wall construction
● Gypsum wall construction
● Solid ceiling construction
On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacity
and air proofs the gap between damper body and installation frame and between installation frame and
wall construction.
● Gypsum wall construction has to be installed according manufacture requirements.
● Installation frame:
● Fasteners:
+3
● a x b = (A + 105
≥ 100
150*
* min. 110 - Concrete/ min. 125 - Aerated concrete
cement lime plates
galvanized plate
+3
mm) x (B + 105
mm)
>100
≥125
≥125
≥ 50
≥ 100
POSITION:
1
Fire damper FDMA PM with Installation frame E1
2
Holder with screws
3
Gypsum plate
4
Mineral stone wool min. density 140 kg/m
5
Fire protection mastic min. thickness 1 mm
69
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
It is possible to use
corresponding number of
holes and screws
Number
Number
Dimensions
ZB1
ZH1
A,B ≤ 400
1
400 < A,B ≤ 800
2
800 < B ≤ 1200
3
1200 < B ≤ 1500
4
1
2
3
4

Advertisement

Table of Contents
loading

Table of Contents