Design .60 with communication and supply device can be complemented with smoke detector
ORS 142 K. For supply and comunnication is used BKN 230-24-MOD, which is used together with
the BF 24TN-ST (BFL 24T-ST, BFN 24T-ST) for communication with control systems using the
Modbus RTU or BACnet MS / TP protocol. The wiring of the line is to be carried out in accordance
with applicable RS485 regulations. Parameterization of the communication is done using DIL
switches. The BKN 230-24-MOD can be installed separately, without a connection to a master
control system, in which case the connection bridge between the terminals 1 and 4 must be
installed. For more information, see the Belimo catalog.
Nominal voltage
Power consumption
Dimensioning
Protection Class
Degree of protection
Ambient temperature
Non-operating temperature
Connection - net
- motor
- terminal board
1
2
3
4
5
6
7
1
S1
S4
2
S2
S3
BAT
Tf
Tf
LED
14 VA (including actuating mechanism with spring return)
13
3
2
1
6
S5
S6
AC 230 V 50/60Hz
3 W (operating position)
II
IP 40
-20°C ... +50°C
-40°C ... +80°C
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm²