Step 2 Set management system parameters.
Figure 6-9 Setting management system parameters
Parameter
Server
Port
Address mode
SSL encryption
Second challenge
authentication
Security certificate
Issue 03 (2020-01-10)
Method 1: When the SmartLogger connects to a Huawei or third-party management
system using the encrypted Modbus TCP protocol, set management system parameters
and click Submit.
Method 2: When the SmartLogger connects to a third-party management system using
the unencrypted Modbus TCP protocol, set Modbus TCP parameters and click Submit.
Copyright © Huawei Technologies Co., Ltd.
Description
Set this parameter to the IP address or domain name of the
management system.
Set this parameter based on the connected management
system.
The value can be Comm. Address or Logical address.
If the communications address of the device connected to the
SmartLogger is unique, you are advised to select Comm.
Address. In other cases, you must select Logical address.
Retain the default value Enable.
NOTE
If this parameter is set to Disable, data exchange between the
SmartLogger and the management system will not be encrypted,
which poses security risks.
Set this parameter based on the connected management
system.
NOTE
If this parameter is set to Disable, the second challenge authentication
result is not checked, and user data may be stolen. Therefore, exercise
caution when setting this parameter.
Optional. Set this parameter only when the certificate has
expired or the customer needs to use their own certificate.
6 WebUI Operations