SmartLogger3000
User Manual
Parsing Mode
The SmartLogger can connect to third-party devices that support IEC103, such as the relay
protection or monitoring device like the transformer substation. The protocol information
points vary depending on vendors. Therefore, you need to obtain a protocol information file
in .cfg format from Huawei and import the file into the SmartLogger for successfully
connecting to a custom device.
The supported device types are IEC103 device 1 to IEC103 device 5. The corresponding
configuration file names are iec103_equip_custom_1.cfg to iec103_equip_custom_5.cfg.
Multiple devices of the same type can be connected.
Step 1 Configure a protocol information point file in .cfg format and import the file to the
SmartLogger.
Figure 6-33 Importing configuration
Step 2 Set access parameters and click Add Devices.
Figure 6-34 Setting access parameters
Parameter
Device Type
Port number
Issue 03 (2020-01-10)
Description
The value can be IEC103 Device 1 to IEC103 Device 5.
Select a value based on the configuration file. For example, if
iec103_equip_custom_1.cfg needs to be imported, select
IEC103 Device 1.
Set this parameter to the COM port connected to the IEC103
device.
Copyright © Huawei Technologies Co., Ltd.
6 WebUI Operations
113