Huawei SmartLogger3000 User Manual page 150

Hide thumbs Also See for SmartLogger3000:
Table of Contents

Advertisement

SmartLogger3000
User Manual
Alarm
Alarm
Alarm
ID
Name
Severity
1105
Device
Major
Address
Conflict
AC SPD
1106
Major
Fault
1107–1
DI1
Major
110
user-defi
ned
alarm to
DI4
user-defi
ned
alarm
1111–1
M1.DI1
Major
114
user-defi
ned
alarm to
M1.DI4
user-defi
ned
alarm
1115
24 V
Major
Power
Failure
Issue 03 (2020-01-10)
Alarm
Cause
Sub-ID
1
The
SmartLogger
RS485 address
conflicts with
the physical
address (RS485
address) or
logical address
for the
connected
southbound
device.
The SPD in the
1
smart array
controller is
faulty.
1
The dry contact
signal from the
peripheral to the
corresponding
DI port of the
SmartLogger is
abnormal.
The dry contact
1
signal from the
peripheral to the
corresponding
DI port of the
SmartModule is
abnormal.
1
The 24 V power
supply in the
smart array
controller is
faulty.
Copyright © Huawei Technologies Co., Ltd.
Suggestions
If the SmartLogger RS485 address
conflicts with the communications
address for the connected southbound
device, choose Settings > Modbus TCP
and change the SmartLogger address, or
choose Maintenance > Device
Mgmt. > Connect Device and change
the southbound device address. If the
southbound device is a solar inverter,
you can change its address on the app.
If the SmartLogger RS485 address
conflicts with the logical address for the
connected southbound device, choose
Settings > Modbus TCP and change
the SmartLogger address.
Check whether the cable to the SPD in
the smart array controller is loose,
disconnected, or reversely connected. If
so, reconnect the cable firmly.
Check whether the SPD in the smart
array controller is faulty. If so, replace
the faulty SPD.
Check the DI port cable connection. If
the cable is loose, disconnected, or
reversely connected, reconnect it firmly.
Check that the relevant device works
properly.
Check the DI port cable connection. If
the cable is loose, disconnected, or
reversely connected, reconnect it firmly.
Check that the relevant device works
properly.
1. Check whether the cable to the 24 V
power supply in the smart array
controller is loose, disconnected, and
connected in reverse. If so, reconnect
the cable securely.
2. Check whether the 24 V power supply
in the smart array controller is faulty.
Replace the faulty power module.
7 Device Maintenance
142