8. Alarms
8.1 Alarms
With SGC 110 it is possible to configure several Shutdown/Electrical trip, Warning and Notification alarms, for example Low oil
pressure shutdown, Overload warning, and more.
An alarm occurs when a pre-configured parameter is out of the preset level. The Alarm LED flashes and the Sounder alarm
activates (if configured). The controller shows the alarm names on the Alarms display and the nature of alarm on Engine status
display.
To acknowledge the alarms, press the Up
All the alarms are activated at the end of Safety monitoring timer. The controller will not send the start command if Warning,
Electrical trip or Shutdown alarms are left unacknowledged.
Alarm types
No.
Alarm actions
1
Shutdown
2
Electrical trip
3
Warning
4
Notification
Alarms and their causes
No.
Alarms
Low Oil Pressure (Sensor)
1
Low Oil Pressure (Switch)
Low Fuel level sensor
2
Low Fuel level switch
High Eng Temp sensor
3
High Eng Temp switch
USER MANUAL 4189341228A UK
and Down
buttons simultaneously.
Description
Load is taken off from the genset and the genset is immediately stopped by skipping the
Engine cooling time.
Load is taken off from the genset, the Engine cooling timer begins, after which the genset
is stopped.
Warning alarms draw the operator's attention to an undesirable condition without affecting
the genset's operation.
The genset cannot be started without acknowledging the Warning alarms
The controller shows the message on the display. The genset start/stop operation is not
affected.
Causes/Indication
Indicates that the oil pressure measured is below the
preset threshold.
Indicates that the oil pressure measured is low through
switch.
Indicates that the amount of fuel level is below the preset
threshold.
Indicates that the amount of fuel level is below the preset
threshold.
Indicates that the engine temperature is above the preset
threshold. This condition is detected only when engine is
on.
Indicates that the engine temperature measured is high
through switch.
Actions
Shutdown
Warning
Shutdown
Warning
Electrical Trip
Notification
Shutdown
Warning
Shutdown
Warning
Electrical Trip
Notification
Shutdown
Warning
Shutdown
Warning
Electrical Trip
Notification