Product Introduction; Product Naming Rules; Packaging Information - Goodwe HT Series User Manual

Photovoltaic grid-tie inverter
Hide thumbs Also See for HT Series:
Table of Contents

Advertisement

3 Product Introduction

3.1 Product Naming Rules

The models involved are as follows:
GW100K-HT
GW110K-HT
GW120K-HT
GW136K-HTH
Model Description (taking GW100K-HT as an example):
1. GW - abbreviation for company name
2. 100K - rated output power
3. HT - model code
3.2 Product Purpose
The HT series is a three-phase transformerless PV string grid-tie inverter, which is the key unit of
the photovoltaic system for connecting the PV string to the grid. The inverter converts the DC
power generated by the photovoltaic module into AC power that meets the parameters of the
local power grid and feeds it into the power grid. The intended use of the inverter is shown in the
diagram below:
A
B
If an isolation transformer is not used on the output side of the inverter to connect to
the power grid, neither the PV+ nor the PV- input terminal of the inverter can be
connected to the ground.
Item
Type
Notes
Monocrystalline silicon, polycrystalline silicon,
A
PV string
thin film PV modules without grounding
B
Inverter
HT series
C
Metering equipment
Electric meter cabinet and distributed power generation system
Different models of TN-S, TN-C, TN-C-S, TT, IT are
D
Utility grid
applicable to the following grid structures
03
kW .H
C
D
Supported grid structure:
The grid structures supported by HT series 100K/110K/120K are TN-S, TN-C, TN-C-S, TT, IT, as
shown in the figure below:
TN-S
TN-C
Transformer
Transformer
Transformer
L1
L1
L2
L2
L3
L3
N
PEN
PE
PE
PE
Inverter
Inverter
The grid structures supported by HT series 136K are TN-S, TN-C, TN-C-S, TT, IT, as shown in the
diagram below:
TN-S
TN-C
Transformer
Transformer
Transformer
L1
L1
L2
L2
L3
L3
N
PEN
PE
PE
PE
Inverter
Inverter
Note: For the TT grid structure, the effective value of the voltage between the neutral wire and
the ground wire must be less than 20V.

3.2 Packaging information

Inverter
Back hanger
Communication
module
Expansion screw
[1] DC connector*: 20 pairs for 100kw, 24 pairs for 120kw&136kw.
[2] Text materials*: Includes business licenses, certification documents, etc.
TN-C-S
TT
Transformer
Transformer
L1
L1
L2
L2
L3
L3
N
N
PE
PE
PE
Inverter
Inverter
TN-C-S
TT
Transformer
Transformer
L1
L1
L2
L2
L3
L3
N
N
PE
PE
PE
Inverter
Inverter
Positive DC
Negative DC
Communication
connector [1]
connector [1]
Handle
Text materials [2]
IT
L1
L2
L3
PE
Inverter
IT
L1
L2
L3
PE
Inverter
terminal
04