For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product
13.

DeviceNET - DESIGN

13.1. Defini on
DeviceNet is an open network system used in the automa)on industry to interconnect control devices for data exchange. It
u)lizes the Common Industrial Protocol over a Controller Area Network media layer and defines an applica)on layer to cover a
range of device profiles. The protocol is standardised under IEC 62026-3.
Connec)ng the control heads to higher bus systems is possible using commercially available gateways.
!
Contact your customer services representa)ve for more informa)on.
Bus line:
Power and data transmiVed on a cer)fied standards-defined four-wire shielded cable
Network topology*:
Tightly defined trunkline/dropline topology, with specified maximum cable lengths according to the cable type. Two kinds of
cable, "thick" and "thin". Data bit rates from 125Kbit/s, 250Kbit/s and 500Kbit/s with maximum cable lengths 500m, 250m and
100m respec)vely. Trunkline/dropline cable budgets are strictly proscribed and must be followed.
The F783E control top module for D-NET is shipped with MACID (module address) set to 63.
* NOTE!
Maximum supply cable length is to be 30m. Control top must be installed in the same building as the control cabinet.
Installa on environment and wiring are influen al on the module's EMC: Thus the installer must secure EMC of the
whole device.
According to Norm EN 61326-1: 2006 (chart 2) DC supply connec ons to the module are treated as input/output
signal lines. For cable lengths greater than 30 m and outdoor applica ons addi onal measures must be implemented
in order to comply with CE
13.2 Electrical connec on op ons —Non-Ex implementa on
Fig 19: Electrical connec on D-NET

13.3. Electrical data

Power supply:
Maximum Load:
Connec ons:
Bulkhead connector: 1 x PG9 threaded socket (M12 plug according to IEC 61076-2-101, 5 pole)
Cable gland version: 1 x PG9 cable gland c/w strain relief for power supply and signals, for cable diameter 3.5—8 mm
Pg 41
As per DeviceNET standard, 11— 25VDC, protected and filtered.
DeviceNET trunkline cable is rated to 8 Amps, check cable lengths are within budget.