For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product
Power consump on at 29.5V (mA):
AS-I Bus power
External Power (Bus load)
Posi on sensors:
3-wire Induc)ve Proximity switch, PNP. Connected to 3-pin headers with latching plugs.
Up to 3 outputs are able to be controlled from a single module. These have a common 24VDC power supply and
Outputs:
ground. These outputs are mapped to bits 0, 1, and 2 of the data byte
Two posi)on switch feedback signals are available. See data mapping in Fig 15 below
Inputs:
CONN#1
Func)on
6-WAY PLUG
1
+24V Supply (link to 3)
2
0V (link to 4)
3
+24V Input
4
0V Input
5
AS-i + (Brown)
6
AS-i - (Blue)
Fig 15: Electrical connec on AS-interface
NOTE!
The Producer/Consumer model
The F783E control module can be considered as having both Inputs and Outputs in both direc)ons, that is both
upstream and downstream from the module. To reduce confusion this document refers to the producer/consumer
model for informa)on transfer. In this model the F783E Module CONSUMES data from the control system or network
(i.e., controls the solenoid) and PRODUCES data for the control system (sends the state of the posi)on switches back to
the control system).
In this respect the control of the solenoid is considered as an Output and the feedback from the switches is considered
an Input. The connec)ons between the control system and the module are agnos)c, and ignored.
Pg 36
Standby
1 switch ON
12
12
CONN#2 & 3
24VDC
3-WAY PLUG
PNP
1
0V
2
+24V
3
Feedback
F783E / F783E 2.0
1 switch ON +
Solenoid energised
35
63.5
34
55
CONN#4
4-WAY PLUG
1
Solenoid 2 control
2
Solenoid common supply
3
Solenoid 1 control
4
Solenoid 3 control
00-ISN-191_Rev C