For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product
12.
AS INTERFACE - DESIGN
12.1. Defini on
AS interface connec on
AS interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors and actuators
(slaves) with a higher-level controller (master).
Connec)ng the control heads to higher bus systems is possible using commercially available gateways.
!
Contact your customer services representa)ve for more informa)on.
Bus line:
Power and data transmiVed on a two-wire unshielded cable
Network topology:
Freely selectable within wide limits. AS-interface can use star or dropline topology or a mixture of both. Bus length limits depend
on the equipment employed, but the nominal limit of 100m* can be increased if using ac)ve bus termina)on and bus repeaters.
The F783E control head module for AS-i uses extended addressing to achieve 62 slaves (A/B addressing) and is designed to be
compa)ble with the AS-i specifica)on 3.0, and is fully backward compa)ble to AS-i 2.1. it can op)onally programmed to operate
with standard addressing for 31 slaves.
* NOTE!
•
Maximum supply cable length is to be 30m. Control top must be installed in the same building as the control cabinet.
•
Installa on environment and wiring are influen al on the module's EMC: Thus the installer must secure EMC of the
whole device.
•
According to Norm EN 61326-1: 2006 (chart 2) DC supply connec ons to the module are treated as input/output
signal lines. For cable lengths greater than 30 m and outdoor applica ons addi onal measures must be implemented
in order to comply with CE
12.2 Electrical connec on op ons —Non-Ex implementa on
Fig 14: Electrical connec on AS-interface
12.3. Electrical data
Power supply:
Maximum Load:
Connec ons:
Bulkhead connector: 1 x PG9 threaded socket (M12 plug according to IEC 61076-2-101, 4 pole)
Cable gland version: 1 x PG9 cable gland c/w strain relief for power supply and signals, for cable diameter 3.5—8 mm
External power supply:
accordance with IEC 364-4-41. it must conform to the SELV standard. The ground poten)al must not have a ground connec)on.
Pg 35
As mandated by the AS-interface protocol, 30VDC, protected and filtered. Use only cer)fied AS-i
power supplies
AS-I network cable is rated to 4 Amps or 8 Amps, check the installa)on for which is installed.
19.2VDC to 31.6VDC. The power supply unit must include a secure disconnec)on in