Programming Data; Device Type; Device Status And Alarms; Device Output Map - Pentair F783E Operating Manual

Control head
Hide thumbs Also See for F783E:
Table of Contents

Advertisement

For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product

13.6. Programming data

13.6.1. Device type

The F783E DeviceNET module is a Group 2 Slave device type "generic".

13.6.2. Device status and alarms

The Input Status Byte describes the state of the module inputs, service flag seBng, FTC and FTO )mers set, module low voltage
alarm, and device failure alarm. The bit paVern is read as follows:
Bit 0
Closed Limit Switch ON
Bit 1
Open Limit Switch ON
Bit 2
Service Flag Set
Bit 3
Double Indica)on Flag
Bit 4
Failed To Open (within set )me)
Bit 5
Failed To Close (within set )me)
Bit 6
Low Voltage
Bit 7
Module Failed

13.6.3. Device output map

The Input Status Byte describes the state of the module inputs, service flag seBng, FTC and FTO )mers set, module low voltage
alarm, and device failure alarm. The bit paVern is read as follows:
Bit 0
Energise Output 1
Bit 1
Energise Output 2
Bit 2
Energise Output 3
Bit 3
Ini)ate ESD func)on
Bit 4
Reset Failed To Open flag
Bit 5
Reset Failed To Close flag
Bit 6
Reset Low Voltage flag
Bit 7
Reset Module Failed flag
Notes:
Only Output 1 is controlled by the ESD command, the other 2 outputs remain as set in the program.
The Service Flag is reset by wri)ng a new service count value to parameter 13 either with a manager program, or via the PLC.
The part of the control byte which resets the error flags is actually interpreted as a four bit binary number. This extends the
range of func)ons of the control byte beyond the eight command limit. The command mapping of this byte segment, called a
"nibble", is below:
Bit Number
7
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
Pg 45
6
5
4
Decimal equivalent
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
F783E / F783E 2.0
0
No Ac)on
1
Reset Fail To Open error flag
2
Reset Fail To Close error flag
3
Reset FTO and FTC error flags
4
Reset Low Voltage error flag
5
Reset LV and FTO error flags
6
Reset LV and FTC error flags
7
Reset Double Indica)on error flag
8
Reset Module Fail error flag
9
Reset MF and FTO error flags
10
Reset MF and FTC error flags
11
No Ac)on - reserved for future use
12
Reset MF and LV error flags
13
Set Node Beacon func)on
14
No Ac)on - reserved for future use
15
No Ac)on - ignored
Ac)on
00-ISN-191_Rev C
20/01/2018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F783e 2.0

Table of Contents