For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product
11.
24V DESIGN
11.1. Electrical connec on op ons—Non-Ex implementa on
Fig 11: Electrical connec on op ons
11.2. Electrical data
22 ... 28 V DC, residual ripple 10 %
Power supply:
20 ... 28 V AC
Connec ons:
Cable gland version: 1 x PG9 cable gland c/w strain relief for power supply and signals, for cable diameter 3.5—8 mm,
Bulkhead connector: 1 x PG9 threaded socket (M12 plug according to IEC 61076-2-101, 4 pole)
Power consump on (mA):
24VDC PNP or NPN
Posi on sensors:
DC
3-wire Induc)ve Proximity switch, PNP.
DC
3-wire Induc)ve Proximity switch, NPN.
AC
2-wire Induc)ve Proximity switch.
Connected to 3-pin headers with latching plugs.
NOTE!
•
Maximum supply cable length is to be 30m. Control top must be installed in the same building as the control cabinet.
•
Installa on environment and wiring are influen al on the module's EMC: Thus the installer must secure EMC of the
whole device.
•
According to Norm EN 61326-1: 2006 (chart 2) DC supply connec ons to the module are treated as input/output
signal lines. For cable lengths greater than 30 m and outdoor applica ons addi onal measures must be implemented
in order to comply with CE
Pg 31
Standby
<1
24VAC
<1
F783E / F783E 2.0
1 switch ON +
1 switch ON
Solenoid energised
30
60
30
70
00-ISN-191_Rev C
20/01/2018