For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer fied product
11.4. Electrical installa on and startup
11.4.1. Cable gland with screw terminals
Procedure:
Open the control head (follow the instruc)ons in chapter 8 "Opening and closing the housing" if in doubt)
⇒
Prepare the cable by stripping back the insula)on to expose approximately 120mm of the cores. Strip each core to expose
⇒
8 to 10mm of bare copper.
Insert the cable through the cable gland un)l the outer sheath is able to be secured by )ghtening the gland
⇒
Twist each core firmly and fold in half before fiBng to the terminals of the 6-way header plug, the correct loca)on for
⇒
each core is printed on the rear of the module, as below in Fig 12.
Tighten the terminal screws.
⇒
Close the housing (follow the instruc)ons in chapter 8 "Opening and closing the housing" if in doubt)
⇒
CONN#1
24VDC
6-WAY PLUG
PNP
1
+24V
2
0V
3
Closed Ind
4
Open Ind
5
Solenoid ±
6
Solenoid ±
Fig 12: DC Electrical connec on screw terminals, example PNP connec on
NOTE!
Ensure IP protec on is maintained!
•
To ensure the control head IP ra)ng is maintained the cable gland nut must be )ghtened securely, the cap O-ring must
be in good condi)on and in place and the relief valve must be fiVed correctly and it's O-ring in place.
•
All unused air connec)ons should be fiVed with a sealing plug
Pg 33
24VDC
24VAC
NPN
0V
24V Phase
+24V
Neutral
Closed Ind
Closed Ind
Open Ind
Open Ind
Solenoid ±
Solenoid ±
Solenoid ±
Solenoid ±
F783E / F783E 2.0
CONN#2 & 3
24VDC
3-WAY PLUG
PNP
1
0V
2
+24V
3
Feedback
CONN#4
2-WAY PLUG
1
Solenoid supply (polarity not cri)cal)
2
Solenoid supply (polarity not cri)cal)
24VDC
24VAC
NPN
+24V
0V
24V Phase
Feedback
Feedback
24VDC, 24VAC
PNP, NPN, AC
00-ISN-191_Rev C
20/01/2018