Chapter 7: Maintenance; Maintenance Schedule - Watts AERCO Benchmark 2.0LN User Manual

Dual-fuel low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0LN:
Table of Contents

Advertisement

Benchmark 2.0LN Dual-Fuel Low NOx Boiler
7.1

MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to keep up efficiency and reliability. For best
operation and life of the unit, the following routine maintenance procedures should be performed
in the time periods specified in Table 7-1. See Appendix I for a complete CSD-1 inspection
check list.
In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits
are available through your local AERCO Sales Representative:
• Annual Maintenance Kit, Part No. 58025-01
• 24-Month Waterside/Fireside Inspection Kit, Part No. 58025-06 (See NOTE below)
The 24-Month Waterside/Fireside Inspection Kit also
includes the items contained in the Annual Maintenance
Kit. Therefore, only Kit Part No. 58025-06 is required
when performing the waterside/fireside inspections.
Appendix K contains recommended spare parts lists for maintenance of the boiler.
TO AVOID PERSONAL INJURY, PRIOR TO SERVICING
ENSURE THAT THE FOLLOWING GUIDELINES ARE STRICTLY
OBSERVED:
DISCONNECT THE AC SUPPLY BY TURNING OFF THE
SERVICE SWITCH AND AC SUPPLY CIRCUIT BREAKER.
SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-
OFF VALVE PROVIDED WITH THE UNIT
ALLOW THE UNIT TO COOL TO A SAFE WATER
TEMPERATURE TO PREVENT BURNING OR SCALDING
Paragraph
Igniter-Injector
7.2
Flame Detector
7.3
7.4
Combustion Calibration
7.5
Testing of Safety Devices
7.6
7.7
Condensate Drain Trap
*Only performed after initial 6 month period after initial startup.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Operation and Maintenance Manual

CHAPTER 7: MAINTENANCE

NOTE
WARNING
Table 7-1: Maintenance Schedule
Item
6 Mos.
*Inspect
(58023)
*Inspect
(66006)
*Check
Burner
*Inspect
12 Mos.
Inspect
Inspect
Check
See CSD-1
-
Chart in
Appendix I
-
-
Inspect &
Clean
GF-127
OMM-0052_0E
Labor
24 Mos.
Time
Replace
15 mins.
Replace
15 mins.
-
1 hr.
-
20 mins.
Inspect
2 hrs.
-
30 mins.
Page 73 of 158