Benchmark 2.0LN Dual-Fuel Low NOx Boiler

APPENDIX E: BOILER DEFAULT SETTINGS

Setup Menu
Password
Language
Unit of Temp
Comm Address
Baud Rate
Configuration Menu
Internal Setpt
Unit Type
Unit Size
Fuel Type
Boiler Mode
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or Combination)
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
Reset Ratio
(If Boiler Mode = Outdoor Reset)
Outdoor Sensor
System Start Tmp
(If Outdoor Sensor = Enabled)
Setpt Lo Limit
Setpt Hi Limit
Temp Hi Limit
Max Valve Position
Pump Delay Timer
Aux Start On Dly
Failsafe Mode
Analog Output
Lo Fire Timer
Setpt Limit Band (If Setpt Limiting = Enabled)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Operation and Maintenance Manual
Table E-1: Boiler Default Settings
MENU & OPTION
FACTORY DEFAULT
0
English
Fahrenheit
0
9600
130°F
BMK Boiler Dual
2000 MBH
Natural Gas
Constant Setpoint
4 – 20 mA / 1-5V
70°F
1.2
Disabled
60°F
60°F
195°F
195°F
Natural Gas = 100%
Propane = 91%
0 min
0 sec
Shutdown
Valve Position 0-10V
CAUTION: DO NOT Change
2 sec
5°F
Page 119 of 158