Natural Gas Combustion Calibration - Watts AERCO Benchmark 2.0LN User Manual

Dual-fuel low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0LN:
Table of Contents

Advertisement

Benchmark 2.0LN Dual-Fuel Low NOx Boiler
CHAPTER 4: INITIAL START-UP
Flame
Observation
Port

4.3 NATURAL GAS COMBUSTION CALIBRATION

The Benchmark 2.0LN Dual-Fuel Boiler is combustion calibrated at the factory prior to shipping.
However, recalibration as part of initial start-up is necessary due to changes in the local altitude,
gas BTU content, gas supply piping and supply regulators. Factory Test Data sheets are
shipped with each unit. These sheets must be filled out and returned to AERCO for proper
Warranty Validation.
It is important to perform the following procedure as outlined. This will keep readjustments to a
minimum and provide optimum performance.
1.
Open the water supply and return valves to the unit and ensure that the system pumps
are running.
2.
Open the natural gas supply valve(s) to the unit.
3.
Set the control panel ON/OFF switch to the OFF position.
4.
Turn on external AC power to the unit. The display will show LOSS OF POWER and the
time and date.
5.
Set the unit to the Manual Mode by pressing the AUTO/MAN key. A flashing Manual
Valve Position message will be displayed with the present rate in %. Also, the MANUAL
LED will light.
Adjust the air/fuel valve position to 0% by pressing the ▼ arrow key.
6.
7.
Ensure that the leak detection ball valve down-stream of the SSOV is open (Figure 4-1).
8.
Ensure that the Fuel Selector Switch (Figure 4-5) is in the NATURAL GAS position.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Page 44 of 158
Operation and Maintenance Manual
Figure 4-3: Flame Observation Port Location
GF-127
OMM-0052_0E
PR2: 04/22/13