6.8 INTERLOCK TESTS

The unit is equipped with two interlock circuits called the Remote Interlock and Delayed
Interlock. Terminal connections for these circuits are located in the I/O Box (Figure 2-9) and are
labeled REMOTE INTL'K IN and DELAYED INTL'K IN. These circuits can shut down the unit in
the event that an interlock is opened. These interlocks are shipped from the factory jumpered
(closed). However, each of these interlocks may be utilized in the field as a remote stop and
start, an emergency cut-off, or to prove that a device such as a pump, gas booster, or louver is
operational.
6.8.1

REMOTE INTERLOCK

1.
Remove the cover from the I/O Box and locate the REMOTE INTL'K IN terminals.
2.
Start the unit in the Manual Mode and set the valve position to 34%.
3.
If there is a jumper across the REMOTE INTL'K IN terminals, remove one side of the
jumper. If the interlock is being controlled by an external device, either open the interlock
via the external device or disconnect one of the wires leading to the external device.
4.
The unit should shut down and display INTERLOCK OPEN.
5.
Once the interlock connection is reconnected, the INTERLOCK OPEN message should
automatically clear and the unit should restart.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
Figure 6-2: Temperature Limit Switch Setting
CHAPTER 6: SAFETY DEVICE TESTING
Page 67 of 158