Remote Setpoint Startup; Direct Drive Modes - Watts AERCO Benchmark 2.0LN User Manual

Dual-fuel low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0LN:
Table of Contents

Advertisement

GF-127
OMM-0052_0E
5.4.2

Remote Setpoint Startup

Since this mode of operation is factory preset and the setpoint is being externally controlled, no
startup instructions are necessary. In this mode, the REMOTE LED will light when the external
signal is present.
To operate the unit in the Manual mode, press the AUTO/MAN switch. The REMOTE LED will
go off and the MANUAL LED will light.
To change back to the Remote Setpoint mode, simply press the AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL LED will go off.

5.5 DIRECT DRIVE MODES

The unit's air/fuel valve position (% open) can be changed by a remote signal which is typically
sent from an Energy Management System (EMS) or from a Building Automation System (BAS).
The Direct Drive mode can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive mode is 4-20 mA/1-5 Vdc. With this setting, a 4
to 20 mA signal, sent by an EMS or BAS is used to change the unit's valve position from 0% to
100%. A 4 mA/1V signal is equal to a 0% valve position, while a 20 mA /5V signal is equal to a
100% valve position. When a 0-20 mA/0-5 Vdc signal is used, zero is equal to a 0% valve
position.
In addition to the current and voltage signals described above, the Direct Drive mode can also
driven by a RS485 Modbus Network signal from an EMS or BAS.
When in a Direct Drive mode, the unit is a slave to the EMS or BAS and does not have a role in
temperature control. Direct Drive can be used to drive single, or multiple units.
If a voltage, rather than current signal is used to control the remote
setpoint, a DIP switch adjustment must be made on the CPU Board
located in the Control Box Assembly. Contact your local AERCO
representative for details.
To enable the Direct Drive Mode, the following menu setting must be made in the Configuration
Menu:
Refer to paragraph 3.3 for instructions on changing menu options.
If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be
entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional
information.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
NOTE
MENU OPTION
Boiler Mode
Remote Signal
CHAPTER 5: MODE OF OPERATION
SETTING
Direct Drive
4-20mA/1-5V,
0-20mA/0-5V, or
Network
Page 59 of 158