Appendix C: Sensor Temperature Resistance - Watts AERCO Benchmark 2.0LN User Manual

Dual-fuel low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0LN:
Table of Contents

Advertisement

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

APPENDIX C: SENSOR TEMPERATURE RESISTANCE

TABLE C-1: Temperature Sensor Resistance Voltage Chart (Balco)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Operation and Maintenance Manual
TEMP (°F)
RES (OHMS)
-40
-30
-20
-10
0
10
20
30
40
50
60
70
1000.0
80
1022.0
90
1044.4
100
1067.0
110
1090.0
120
1113.3
130
1137.0
140
1160.9
150
1185.2
160
1209.5
170
1234.7
180
1260.0
190
1285.6
200
1311.4
210
1337.7
220
1364.2
230
1391.0
240
1418.2
250
1445.7
VOLTS*
779.0
1.93
797.5
1.96
816.3
1.99
835.4
2.02
854.8
2.05
874.6
2.07
894.7
2.10
915.1
2.12
935.9
2.15
956.9
2.17
978.3
2.20
2.23
2.25
2.27
2.30
2.32
2.34
2.36
2.39
2.41
2.43
2.45
2.47
2.50
2.52
2.54
2.56
2.58
GF-127