Chapter 4-Mechanical Installation; Electrical Installation Warnings And Cautions; Standard Mounting Instructions - Eaton PowerXL DM1 Series Installation Manual

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 4—Mechanical installation
N
ote:
All following information is strongly recommended
but is not necessary if sufficient system design and
validation has been completed.
This chapter contains all of the information required to
properly install and prepare the PowerXL Series VFD for
operation. The contents are listed to serve as a list of
tasks needed to complete the installation. Included in this
section are:
Installation environment;
Standard mounting position and clearance;
Option card installation;
NEMA 1 kit installation; and
Remote mount keypad kit installation.

Electrical installation warnings and cautions

WARNING
Carry out wiring work only after the frequency inverter
has been correctly mounted and secured.
WARNING
Electric shock hazard—risk of injuries!
Carry out wiring work only if the unit is de-energized.
Debounced inputs may not be used in the safety
circuit diagram.
Fire hazard!
Only use cables, protective switches, and contactors that
feature the indicated permissible nominal current value.
Debounced inputs may not be used in the safety
circuit diagram.
According to product standard IEC/EN 61800-5-1, an
additional equipment grounding (PE) conductor of the same
cross-sectional area as the original protective earthing
conductor must be connected, or the cross-section of
the equipment grounding conductor must be at least
10 mm
 Cu.
2
CAUTION
CAUTION
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Chapter 4—Mechanical installation
WARNING
The components in the drive's power section remain
energized after the supply voltage has been switched
off. After disconnecting the supply, wait at least
five minutes before removing the cover to allow the
intermediate circuit capacitors to discharge.
Pay attention to hazard warnings!

Standard mounting instructions

Select the mounting location based on requirements
listed in this chapter.
Mounting surface must be a flat, non flammable surface.
Mounting orientation can be vertical, horizontal or inclined
(refer to mounting orientation illustration Figure 7).
DIN rail mounting is only applicable for vertical mounting,
while screw mounting is applicable for vertical mounting,
horizontal mounting and inclined mounting.
PowerXL Series open drives may be mounted side-by-
side or stacked vertically, as outlined in this chapter.
Surface must be strong enough to support the drive and
not subject to excessive motion or vibration.
Mark the location of the mounting holes on the mounting
surface.
Using fasteners appropriate to your VFD and mounting
surface, securely attach the VFD to the mounting surface
using all mounting hole locations.
When mounting one unit above the other, the lower unit air
outlet must be directed away from the inlet air used by the
upper one. The clearance between the upper and lower unit
should equal C + D. See illustrations above Table 16.
Mounting dimensions
Refer to Appendix C for drive dimensions.
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents