Connecting Communications Cables; Installing A Parallel System - Huawei UPS5000-E FM Series User Manual

Hide thumbs Also See for UPS5000-E FM Series:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Figure 3-39 Cable connection for an NC EPO switch
Figure 3-40 Cable connection for an NO EPO switch

3.2.7 Connecting Communications Cables

Procedure
Step 1 Connect the external network management device to the RS485 port of the
monitoring interface card.
Step 2 Connect the network port on a PC to the FE port of the monitoring interface card.
----End

3.3 Installing a Parallel System

Issue 02 (2020-11-10)
Figure 3-40
shows the cable connections for an NO EPO switch.
NO TE
● When the EPO switch is in the NC state, remove the jumper between EPO_NC and
EPO_12V before connection. When the EPO switch is turned off, EPO is triggered.
● When the EPO switch is in the NO state, ensure that the jumper is connected between
EPO_NC and EPO_12V. When the EPO switch is turned on, EPO is triggered.