Huawei UPS5000-E FM Series User Manual page 35

Hide thumbs Also See for UPS5000-E FM Series:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Indicator
Alarm indicator
Fault indicator
Functions
The bypass module supplies power in the following cases:
If the UPS is set to ECO mode and the bypass voltage is within the specified range,
the UPS works in bypass mode.
If the power module overload times out, the UPS transfers to bypass mode.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.
Specifications
Issue 02 (2020-11-10)
Color
Yellow
Red
Dimensions (H x W x D): 130 mm x 420 mm x 500 mm
Weight: 19 kg
Rated output capacity: 200 kVA
Copyright © Huawei Technologies Co., Ltd.
Status
Blinking at short
intervals
Off
Steady on
Off
Steady on
Off
2 Overview
Description
The bypass is not
configured or the DSP
software is being
upgraded (blinking at 4
Hz, on for 0.125s and off
for 0.125s).
The bypass software is
being upgraded.
A minor alarm is
generated for the bypass.
There is no minor alarm
for the bypass, or the
software is being
upgraded.
A critical alarm is
generated for the bypass.
There is no critical alarm
for the bypass, or the
software is being
upgraded.
27