User Manual
5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to
bypass mode; if the bypass is not normal, the UPS supplies no power. Before
shutting down the UPS, ensure that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
●
Issue 02 (2020-11-10)
NO TICE
On the LCD
On the LCD main screen, tap Common Functions. Tap Inv. OFF.
NO TE
To shut down the inverter on the Maintenance screen, tap System Info >
Maintenance.
Figure 5-5 Normal bypass
NO TE
After you shut down the inverter, the Bypass mode alarm is displayed on the LCD.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
147