UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Item
Installation
time
Maintenance
period(d)
Cell float
voltage(V/
cell)
Cell equalized
volt.(V/cell)
Dis. curr. 0.1C
EOD(V/cell)
Dis. curr. 0.3C
EOD(V/cell)
Dis. curr. 0.5C
EOD(V/cell)
Dis. curr. 1.0C
EOD(V/cell)
Sched.
shallow dis.
test
Sched.
shallow dis.
test time
Sched.
shallow dis.
test
interval(d)
Shallow dis.
test dis.
ratio(%)
Issue 02 (2020-11-10)
Description
A battery maintenance
reminder is displayed when
the maintenance time
(counted from the
installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
Specifies the battery float
charging voltage.
Specifies the battery
equalized charging voltage.
Specifies the EOD threshold
when the discharge current is
0.1C, 0.3C, 0.5C, or 1.0C
respectively.
When certain conditions are
met, the charger shuts down,
and batteries supply power
to loads. The system records
the battery discharge data as
a reference for battery
capacity and lifespan.
Specifies the time for a
scheduled shallow discharge
test.
Specifies the interval for a
scheduled shallow discharge
test.
Specifies the proportion of
the discharge capacity to the
total discharge capacity. The
value is configurable in any
mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
N/A
N/A
0
0–365
2.25
2.23–2.30
2.35
2.30–2.40
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
Disable
Disable,
Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
60
30–90
20
10–50
112